Description
Environment
GENERAL CHARACTERISTICS
Electrical Specifications | |
---|---|
Nominal voltage | 415 V – 50 Hz |
Capacity Tolerance | -5%, +5% |
Connection Type | Three-phase |
Power Loss | < 2.5 W/kVAr |
Maximum Allowable Current (with thermal protection included) |
1.43 In |
Maximum Allowable Voltage | 1.27 x Un, 8h every 24h |
Overload Protection | CHL Protection Alarm (Capacitor Harmonic Load) |
Isolation Voltage | 690 V |
Shock Withstand Voltage | 8 kV |
Box | |
---|---|
Degree of protection | IP42 |
Color | RAL 7035 |
Degree of Mechanical Resistance | IK10 |
Varmetric Relay | |
---|---|
Genius® | Genius® B106 (other options available) |
Head Protection | |
---|---|
With Main Switch | Rotary Handle Switch-Disconnector The compensation bank must be protected upstream by a circuit breaker |
With Circuit Breaker | Modular circuit breaker up to 25 kVAR Molded case circuit breaker starting from 37.5kVAR |
Steps | |
---|---|
Type of Capacitors | VARCap® 480 V – 50 Hz Maximum Overload: Up to 2.0 In Maximum Inrush Current: ≤500 In Operational Ambient Temperature: -40°C – +60°C Overvoltage Protection for all 3 Phases Discharge Resistance 50 V – 1 min |
Contactors | KMC Range, dedicated to capacitor switching |
Step protection | Protection provided by the head circuit breaker |
Temperature Control | |
---|---|
Temperature Control | By Thermostat & by Genius® controller |
Communication | |
---|---|
ModBus | RS485 (optional) |
Installation | |
---|---|
Auxiliary Power Supply | 230 V AC – 50Hz |
CT (Not included) | >5 VA – secondary1 A or 5 A To be installed upstream of the load and the compensation bank |
Emergency Group Contact | Not available |
Alarm Contact | Available for remote alarm reporting |
Dimensions | |
---|---|
Power up to xxkVAR | Panel C1 – HxLxP : 470 X 392 X 205 |
Power up to xxkVAR | Panel C2 – HxLxP : 600 X 462 X 205 |
Power up to xxkVAR | Panel C3 – HxLxP : 600 X 650 X 260 |
Environment
GENERAL CHARACTERISTICS
Electrical Specifications | |
---|---|
Nominal Voltage: | 415 V – 50 Hz |
Capacity Tolerance: | -5%, +5% |
Connection Type: | Three-phase |
Power Loss | < 2.5 W/kVAr |
Maximum Allowable Current (with thermal protection included) | 1.43 In |
Maximum Allowable Voltage | 1.27 x Un, 8h every 24h |
Overload Protection | CHL Protection Alarm (Capacitor Harmonic Load) |
Isolation Voltage | 690 V |
Shock Withstand Voltage | 8 kV |
Box | |
---|---|
Degree of protection | IP42 |
Color | RAL 7035 |
Degree of Mechanical Resistance | IK10 |
Varmetric Relay | |
---|---|
Genius® | Genius® B106 (other options available) |
Head Protection | |
---|---|
With Main Switch | Rotary Handle Switch-Disconnector The compensation bank must be protected upstream by a circuit breaker |
With Circuit Breaker | Modular circuit breaker up to 25 kVAR Molded case circuit breaker starting from 37.5kVAR |
Steps | |
---|---|
Type of Capacitors | VARCap® 480 V – 50 Hz Maximum Overload: Up to 2.0 In Maximum Inrush Current: ≤500 In Operational Ambient Temperature: -40°C – +60°C Overvoltage Protection for all 3 Phases Discharge Resistance 50 V – 1 min |
Contactors | KMC Range, dedicated to capacitor switching |
Step protection | Protection ensured by the head circuit breaker |
Temperature Control | |
---|---|
Temperature Control | By Thermostat by Genius® controller |
Communication | |
---|---|
ModBus | RS485 (optional) |
Installation | |
---|---|
Auxiliary Power Supply | 230 V AC – 50Hz |
CT (Not included) | >5 VA – secondary1 A or 5 A To be installed upstream of the load and the compensation bank |
Emergency Group Contact | Not available |
Alarm Contact | Available for remote alarm reporting |
Dimensions | |
---|---|
Power up to xxkVAR | Panel C1 – HxLxP : 470 X 392 X 205 |
Power up to xxkVAR | Panel C2 – HxLxP : 600 X 462 X 205 |
Power up to xxkVAR | Panel C3 – HxLxP : 600 X 650 X 260 |