Thanks to its capacitive touch keys, it offers an IP64 front panel protection rating of the cabinet, allowing it to be installed in the most severe operating conditions (mining industries, food industries, etc.).

The instrument has two slots for inserting extension modules, which allow for expanding the instrument’s functionalities.

Applications

  • Data collection
  • Energy management
  • Power quality

  • Remote monitoring

Main features

Measurement:

  • V / A / P / Q / S / F / PF / DPF – RMS and fundamental

  • Maximum Indicator (Demand)
  • Value Max./Min.
  • Charging profile

Power quality:

  • Up to the 63rd harmonic
  • Sequential components
  • Unbalance
  • Peak factor and K factor
  • Phase diagram

Energy measurement:

  • Bi-directional energy
  • Reactive energy on 4 quadrants
  • Energy by tariff
  • Fundamental energy

Available Modules (optional):

  • GPRS
  • Wifi
  • M-Bus
  • RS-485 : Modbus-RTU

  • RS232
  • BACnet/IP
  • BACnet/MSTP
  • Profibus-DP
  • Ethernet: Modbus-TCP

  • Ethernet: Data logger with embedded Web server

  • 2 relay outputs
  • 2 analog outputs
  • 4 DC digital inputs
  • 2 AC digital inputs
  • 2 analog inputs (4-20mA)
  • 2 analog inputs (PT100)

Functions

Network
  • TN, TT, IT networks

Data collection
  • Maximeter recording (Demand)
  • Max./Min. values sheet.
  • Limit exceedance recording
  • SOE Recording

Optional modules
  • See comparison table

Optional modules
  • See comparison table

Communication
  • Modbus-RTU, Modbus-TCP, Profibus-DP, BACnet/IP, BACnet/MSTP

Accuracy
  • Active energy: 0.2S

  • Voltage: 0.1%

  • Current: 0.1%

Energy quality
  • Compliant with EN50160

  • THD

  • Harmonics up to the 63rd

  • Unbalance

  • Sequential components

  • Voltage dips

  • overvoltage

  • Interruptions

  • Flicker

  • Transients

  • Peak factor and K factor

  • Displaying waveforms

Screen Samples

Technical characteristics

Accuracy
  • V/A: 0.1%

  • P / Q / S / PF: 0.2%

  • F: +/- 0.01Hz

  • +/- kWh: Class 0.2S

  • +/- kVarh: Class 2

Input voltage
  • Nominal value: 3x230V / 400V

  • Overvoltage: Continuous : 1.2Vn. Instant: 2Vn/10s

  • Load: <= 0.1VA (per phase)

  • Impedance: >= 1.7MΩ

  • Frequency: 45Hz~65Hz

Voltage Input current
  • Nominal value: 1A ou 5A AC

  • Overload: Continuous: 1.2In. Instant: 10In/5s

  • Load: <= 0.1VA (per phase)

  • Impedance: < 20mΩ

Power supply
  • Voltage range: 80~270V AC/DC

  • Consumption: <= 10VA

Communication port
  • RS485, Modbus-RTU, 2 wires, up to 38.4kbps

Energy pulse output
  • 1 optocoupler output, pulse width (80+/-20%) ms

Digital input
  • 2 active entries 220V AC Isolation : 2000VAC

Relay output
  • 2 Relay outputs 5A/250V AC or 5A/30V DC. Isolation : 2500VAC

Environmental resistance
  • Operating temperature: -10°C~60°C
  • Storage temperature: -25°C~70°C

  • Relative humidity: 5-95% without condensation

  • Altitude: <=2500m

Dielectric strength
  • According to IEC61010-1

Degree of IP protection
  • Front IP64, Back IP20