Dimensions and Installation

Dimensions (mm) RCM100 RCM150 RCM200
A. Size of Window A 135 165 210
B. Size of Window B 100 150 200
C. Outer Diameter of the Coil 151 181 226
D. Coil Section 8
E. Total Length of the Supply Cable 2000
F. Length of the Coil 395 525 665

Tolerance on dimensions: A, B, C, F: +5mm, D: +2mm, E: +10mm

Position Sensitivity

Conductor PositionTypical Error(%)
Adjacent to Immersion Mechanism 0.5%
Adjacent to Inner Coil Edge 0.8%
Adjacent to Opposite Clip 1%

Reference Table

Commercial Reference Nominal Current Ratio @ 50 Hz Diameter Color
RCM-200B-050 6000A 50mV/kA 200mm Blue
RCM-150B-85 3000A 85mV/kA 150mm Blue
RCM-100B-85 1000A 85mV/kA 100mm Blue
RCM-1000-100 1000A 100mV/kA 100mm Orange

Technical characteristics

Characteristics
Manufacturing Tolerance <0,5% (calibrated)
Temperature Drift Coefficient of Sensitivity <100ppm/°C
Temperature Drift Coefficient of Internal Resistance <3800ppm/°C Please contact us for exact value
Measurement Accuracy Class 0.5% (Vertically Centered Position)
Internal Resistance 50-250 Ω
Position Error <1%
Output at OA (Zero Drift) <0.05mV
Phase Error <0.5° (45Hz – 65Hz)
Linearity +0,1%(1% – 100%)
Bandwidth (3dB) 1Hz – 20KHz
Operating Temperature -40°C – 85°C
Coil Section 8mm
Cable Length (default) 2m (other lengths on request)
Materials
Coils and Cables Flame-retardant thermoplastic rubber, UL 94 V-0 class
Closure System PC, ABS, class UL 94 V-0
Color (coil) Blue (standard) or Orange
Isolation
Applicable Voltage Range 1000V CATIII, 600V CATIV
Dielectric Strength 7400Vac @ 50/60Hz 1Min
Certifications CE, Cmim, IP68, Rohs 2.0

Contact us for special characteristics and dimensions if needed