Environment

  • Installation: Indoor

  • Ambient Temperature: -5°C to 45°C

  • Average Daily Temperature: Maximum +35°C

  • Humidity: Up to 95%
  • Maximum Altitude: 2000m

GENERAL CHARACTERISTICS

Electrical Specifications
Nominal Voltage: 415 V – 50 Hz
Capacity Tolerance: -5%, +5%
Connection Type: Three-phase
Power Loss < 2.5 W/kVAr
Maximum Allowable Current (with thermal protection included) 1.43 In
Maximum Allowable Voltage 1.1 x Un, 8h every 24h
Isolation Voltage 690 V
Nominal Impulse Withstand Voltage (Uimp) 8 kV
Box
Degree of protection IP42
Color RAL 7035
Degree of Mechanical Resistance IK10
Head Protection
With Main Switch Rotary Handle Switch-Disconnector
The compensation bank must be protected upstream by a circuit breaker
With Circuit Breaker Molded case circuit breaker
Rotary handle on demand
Components
Type of Capacitors VARCap® 415 V – 50 Hz
Maximum Overload: Up to 2.0 In
Maximum Inrush Current: ≤500 In
Operational Ambient Temperature: -40°C – +60°C
Overvoltage Protection for all 3 Phases
Discharge Resistance: 50 V – 1 min
Signaling
3 LED voltage presence indicators on the front panel