Environment

  • Installation: Indoor

  • Ambient Temperature: -5°C to 45°C

  • Average Daily Temperature: Maximum +35°C

  • Humidity: Up to 95%
  • Maximum Altitude: 2000m

GENERAL CHARACTERISTICS

Electrical Specifications
Nominal Voltage: 415 V – 50 Hz
Capacity Tolerance: -5%, +5%
Connection Type: Three-phase
Power Loss < 2.5 W/kVAr
Maximum Allowable Current (with thermal protection included) 1.43 In
Maximum Allowable Voltage 1.27 x Un, 8h every 24h
Overload Protection CHL Protection Alarm (Capacitor Harmonic Load)
Isolation Voltage 690 V
Shock Withstand Voltage 8 kV
Box
Degree of protection IP42
Color RAL 7035
Degree of Mechanical Resistance IK10
Varmetric Relay
Genius® Genius® B106 (other options available)
Head Protection
With Main Switch Rotary Handle Switch-Disconnector
The compensation bank must be protected upstream by a circuit breaker
With Circuit Breaker Modular circuit breaker up to 25 kVAR
Molded case circuit breaker starting from 37.5kVAR
Steps
Type of Capacitors VARCap® 480 V – 50 Hz
Maximum Overload: Up to 2.0 In
Maximum Inrush Current: ≤500 In
Operational Ambient Temperature: -40°C – +60°C
Overvoltage Protection for all 3 Phases
Discharge Resistance 50 V – 1 min
Contactors KMC Range, dedicated to capacitor switching
Step protection Protection ensured by the head circuit breaker

 

Temperature Control
Temperature Control By Thermostat by Genius® controller
Communication
ModBus RS485 (optional)
Installation
Auxiliary Power Supply 230 V AC – 50Hz
CT (Not included) >5 VA – secondary1 A or 5 A
To be installed upstream of the load and the compensation bank
Emergency Group Contact Not available
Alarm Contact Available for remote alarm reporting
Dimensions
Power up to xxkVAR Panel C1 – HxLxP : 470 X 392 X 205
Power up to xxkVAR Panel C2 – HxLxP : 600 X 462 X 205
Power up to xxkVAR Panel C3 – HxLxP : 600 X 650 X 260