CMM-R6D
Multifunction measurement center

CMM-R6D is the ideal solution for monitoring transformer stations and TGBTs. It allows for measuring the main electrical parameters of the network, ensuring bidirectional energy counting, and measuring earth leakage current, ambient or contact temperature, in addition to remotely controlling and reporting device states. Moreover, it enables the separation of active and reactive energy consumption from the "Normal" network from those produced by the backup generator.

  • Accuracy: 0.5s
  • Input for leakage current measurement: Ir
  • Temperature measurement input: PT100
  • Energy measurement function for Normal / Backup modes
  • Display of neutral current
  • 4 Tariffs
  • Harmonics
  • RS-485 Modbus Port
  • 1 Impulse Output
  • DIN rail mounting
  • 4 Inputs / 2 Outputs module (optional)
Standards:
  • IEC 62052-11
  • IEC 61557-12
  • IEC 62053-21/22/23
  • IEC 50470-1/3
  • IEC 61010-1/2/31
Certifications

Description

The CMM-R6D measurement center allows for measuring the main electrical parameters of the network, ensuring bidirectional energy counting, and analyzing some parameters of electrical signal quality. It is equipped with a ground leakage current measurement input and a PT100 temperature measurement input. It can also be equipped with a module of 4 TOR inputs and two relay outputs for the control and monitoring of field equipment. The device also features a power measurement function for the backup source, which can be triggered by an external signal It can be easily integrated into any supervision system or energy management system to monitor installation or energy quality.

It is primarily intended for monitoring electrical substations (transformer substations) and for energy management and monitoring of electrical installations requiring mounting on rails (distribution panels in tertiary or residential buildings), mounting in drawers of detachable panels (mining industries, etc.), monitoring of generators and motor starters with measurement of earth leakage current and equipment temperature measurement (generators, capacitor banks, MCC panels, machine tools, ovens, etc.), etc.

Applications

Functions

Network
  • TN, TT, IT networks

Communication
  • RS485 Interface

  • Modbus-RTU Protocol

Accuracy
  • Active energy: 0.5S

  • Voltage: 0.2%

  • Current: 0.2%

Installation and Connection

Measured and displayed parameters

Technical characteristics

Accuracy
  • V/A: 0.2%

  • P / Q / S / PF: 0.5%

  • F: +/- 0.01Hz

  • +/- kWh: Class 0.5S

  • +/- kVarh: Class 2

Input voltage
  • Nominal value: 3×230/400V

  • Overvoltage: Continuous : 1.2Vn. Instant: 2Vn/10s

  • Load: <= 0.1VA (per phase)

  • Impedance: >= 1.7MΩ

  • Frequency: 45Hz~65Hz

Input current
  • Nominal value: 1A ou 5A AC

  • Overload: Continuous: 1.2In. Instant : 2In/5s

  • Load: <= 0.2VA (per phase)

  • Impedance: < 20mΩ

Residual current input
  • Residual current input: 1A/1mA AC (External differential toroidal)

Temperature measurement
  • PT100

Power supply
  • Voltage range: 80~270V AC / 50~60Hz

  • Consumption: <= 5VA

Communication port
  • RS485, Modbus-RTU, 2 cables, up to 9600bps

Energy pulse output
  • 1 optocoupler output,

  • pulse width: 80ms (+/-20%)

Optional module (EK1)
  • Digital inputs: Dry digital inputs, Isolation: >=2kVAC

  • Relay outputs: Contact 5A/250V AC or 5A/30V DC

Ambient conditions
  • Operating temperature : -25°C~70°C
  • Storage temperature: -30°C~80°C

  • Relative humidity: <=95% non-condensing

  • Altitude: <=2500m

Dielectric strength
  • According to IEC61010-1

Display
  • Display type: LCD

Dimensions

Dimensions

Product Documentations