What are the 10 levels of protection provided by our compensation cabinets to ensure optimal safety ?
- Individual protection of each step by fuses or circuit breaker
- Fast ceramic discharge resistor integrated in each capacitor to avoid the risk of electrocution
- Environmental protection : no oil is used in our capacitors : biodegradable semi-dry resin
- Individual protection of each step against the phenomenon of harmonic resonance and overloads
- General protection against short-circuits by a magneto-thermal circuit breaker integrated in the capacitor bank (optional)
- Protection against overloads and overpressures by internal fuse in each capacitor
- Triple protection against overheating by external temperature sensor, internal measurement of temperatur by the PFC controller and temperature sensor in each detuned reactor
- Protection against overcompensation and under compensation thanks to the measurement of currents and voltages on the 3 phases simultaneously
- Protection against fire (optional)
- General residual current protection of the capacitor bank, to ensure safety against any ground current (optional).