References
CMM-61-C
CMM-61h-C
CMM-61-R
Rogowski current inputs (flexible coils)
CMM-61h-C
Rogowski current inputs and harmonic measurement by order (up to 50th)
Applications
Data collection
Energy management
Remote monitoring
Main features
Measurement:
V / A / P / Q / S / F / PF / DPF – RMS and fundamental
P/Q/S powers per phase
Total P/Q/S powers (CMM-61hR and CMM-61C)
Maximum Indicator (Demand)
Max./Min Value
Power quality:
Voltage and current THD
Harmonics up to the 51st order (CMM-61hR and CMM-61hC)
Unbalance
Energy measurement:
- Bi-directional energy
- Reactive energy on 4 quadrants
- Energy by tariff
Inputs/Outputs:
1 energy pulse
2 digital inputs
2 relay outputs
Measured and displayed parameters
Measured Values
Single voltages: V1, V2, V3 (and average value displayed on CMM-61h only).
- Composite voltages: U12, U23, U31 (and average value displayed on CMM-61h only).
Current: I1, I2, I3 (and average value displayed on CMM-61h only).
Power: Active Power, Reactive Power, Apparent Power per phase (and total value displayed on CMM-61h only).
- Energy: Imported Active Energy, Exported Active Energy, Imported Reactive Energy, Exported Reactive Energy, Apparent Energy.
When the energy value exceeds 9,999,999.9 kWh, the meter automatically resets to “0”. Power factor: Power factor PF and cos phi (fundamental power factor – DPF): Average value of each phase (and total value displayed on CMM-61h only).
- Frequency: Network frequency.
Refresh Rate
Refresh Rate: 500ms
Harmonics
THD: Harmonic distortion rate THD of current and voltage for each phase
Harmonics : Current and voltage harmonics by order, up to the 51st order (CMM-61h only)
Max / min
- Voltage: Per phase.
(Average value of the three phases displayed on CMM-61h only) - Current: Per phase.
(Average value of the three phases displayed on CMM-61h only) - Power: Active Power, Reactive Power, Apparent Power per phase.
(Total value displayed on CMM-61h only)
Unbalance
Voltage: value displayed on CMM-61h only.
Current: value displayed on CMM-61h only.
Demand / Maximum Indicator
- Current: Per phase.
(Average value of the three phases displayed on CMM-61h only). - Power: Active Power, Reactive Power, Apparent Power per phase.
(Total value displayed on CMM-61h only).
Accuracy and Environment
Measurement Accuracy
Current (reading value)
- CMM-61C: ±0.3%
- CMM-61R: ±0.5%
Guaranteed current measurement accuracy range (full scale)
- CMM-61C: 0.5% FS~100%
- CMM-61R: 2% FS~100%
Voltage: 0.2%(30~600V AC)
Frequency: 0.01%(45~65Hz)
- Power factor and Cos phi: ±0.005
- Active and Apparent Power: IEC62053-22 – Class 0.5S
- Reactive Power: IEC62053-21 – Class 2S
- Active Energy: IEC62053-22 – Class 0.5S
- Reactive Energy: IEC62053-21 – Class 2S
Environment
Operating Temperature: -25℃~+60℃
Storage Temperature: -40℃~+85℃
Relative Humidity: 5~95% RH, 50℃ (non-condensing)
Pollution Degree: 2
Overvoltage Capacity: CAT III 1000V, (indicated for network voltages below 277 / 480VAC))
Dielectric Strength: IEC61010-1
Altitude: 3000m Max
Protection Rating: IP20 Compliant with IEC 60629