CMM-61h-C
Current inputs /1A – /7A
CMM-61h-R
Rogowski current inputs
Applications
Data collection
Energy management
Remote monitoring
Main features
Measurement:
Maximum Indicator (Demand)
Max./Min Value
Power quality:
Voltage and current THD
Unbalance
Energy measurement:
- Bi-directional energy
- Reactive energy on 4 quadrants
- Energy by tariff
Inputs/Outputs:
1 energy pulse
2 digital inputs
1 relay output
Measured and displayed parameters
Measured Values
Single voltages: V1, V2, V3
- Composite voltages: U12, U23, U31 and average value.
Current: I1, I2, I3 and average value.
Power: Power: Active Power, Reactive Power, Apparent Power (total et per phase)
- Energy: Imported Active Energy, Exported Active Energy, Imported Reactive Energy, Exported Reactive Energy, Apparent Energy.
When the energy value exceeds 9,999,999.9 kWh, the meter automatically resets to “0”. Power factor: Power factor PF and cos phi (fundamental power factor – DPF): Average value of each phase and all phases.
- Frequency: Network frequency.
Refresh Rate
Refresh Rate: 500ms
Harmonics
Voltage: Harmonic distortion rate THD of each phase
Current: Harmonic distortion rate THD of each phase
Max / min
- Voltage: Per phase.
- Current: Per phase.
- Power: Active Power, Reactive Power, Apparent Power(sum of all phases and each phase)
Unbalance
Voltage: Per phase.
Current: Per phase.
Demand / Maximum Indicator
- Current: Per phase.
- Power: Active Power, Reactive Power, Apparent Power(sum of all phases and each phase)
Accuracy and Environment
Measurement Accuracy
Current (reading value)
- CMM-61C: ±0.3%
- CMM-61R: ±0.5%
Guaranteed current measurement accuracy range (full scale)
- CMM-61C: 0.5% FS~100%
- CMM-61R: 2% FS~100%
Voltage: 0.2%(30~600V AC)
Frequency: 0.01%(45~65Hz)
- Power factor and Cos phi: ±0.005
- Active and Apparent Power: IEC62053-22 – Class 0.5S
- Reactive Power: IEC62053-21 – Class 2S
- Active Energy: IEC62053-22 – Class 0.5S
- Reactive Energy: IEC62053-21 – Class 2S
Environment
Operating Temperature: -25℃~+60℃
Storage Temperature: -40℃~+85℃
Relative Humidity: 5~95% RH, 50℃ (non-condensing)
Pollution Degree: 2
Overvoltage Capacity: CAT III 1000V, (indicated for network voltages below 277 / 480VAC))
Dielectric Strength: IEC61010-1
Altitude: 3000m Max
Protection Rating: IP20 (Compliant with IEC 60629)