CMM-R5M – Data Logging Measurement Unit Main features:Measurement:V/A/P/Q/S/F/PFMaximeter of currents and active powerPower quality:THDU and THDIUp to the 25th harmonicEnergy measurement:Bidirectional energyReactive energy in 4 quadrantsEnergy by tariff (3 tariffs)Special features:32 GB SD memory1 relay outputCurrent measurement inputs with Rogowski coilInternal clockFunctionsNetwork TN, TT, IT networks Single-phase or Three-phase BT et HT Communication RS485 Interface Modbus-RTU Protocol Accuracy Active energy: 0.5S Voltage: 0.2% Current : 0.5% Technical characteristicsDisplay 2-inch color TFT Accuracy V/A: 0.2% P / Q / S / PF: 0.5% F: 2% +/- kWh: Class 0.5S +/- kVarh: Class 2 Input voltage Nominal value: 100 – 500V(LL) Overvoltage: Continuous : Continuous : 1.2Vn. Instantaneous: 2Vn/10s Load: <= 0.1VA (per phase) Impedance: >= 1.7MΩ Frequency: 45Hz~65Hz Input currentRogowski coil RCM16 : 100A-85mv/A @ 50HZ± 0.5%Rogowski coil RCM36 : 600A-85mv/A @ 50HZ± 0.5%Rogowski Coil RCM100: 1000A-85mv/A @ 50HZ± 0.5%Rogowski coil RCM150: 3000A-85mv/A @ 50HZ± 0.5%Rogowski coil RCM200: 6000A-50mv/A @ 50HZ± 0.5%Current input characteristics Nominal value – Primary current: Adjustable from 0.1A to 9999A Overload: 600mv during 10s/h Measuring range: 1/225mv – 333mv Power supplyOperating range: 85~265V AC / 50~60Hz / 100~370V DC Consumption: <= 5VA Communication port RS485, Modbus-RTU, 2-wire, up to 57600bps Relay output 1 relay output Ambient conditions Operating temperature: -25°C to +55°C Storage temperature: -40°C to +85°C Relative humidity: 95% RH at 50°C(under-condensation) Pollution degree: 2 Overvoltage category: Cat. III for networks up to 277/480VAC Dielectric strength: According to IEC61010-1, Double insulation of the front panel Altitude: 3000m Max Degree of protection: IP20 according to IEC 60529 Electromagnetic compatibilityElectrostatic discharge: Level IV(IEC61000-4-2)Radiation immunity: Level III (IEC61000-4-3)Transient immunity: Level IV (IEC61000-4-4)Lightning immunity: Level IV (IEC61000-4-5)Conducted immunity: Level III (IEC61000-4-6)Immunity to power frequency magnetic fields: 0.5mT (IEC61000-4-8)Conducted and radiated emissions: Class B (EN55022)Installation and ConnectionDimensions By admin|2024-09-15T18:14:54+00:00September 15, 2024|Comments Off on CMM-R5M – Data Logging Measurement Unit Partagez cet article, Choisissez votre Plateforme! LinkedInWhatsAppEmail About the Author: admin