Technical Specifications

Transformation ratio
  • From 400/5A to 3000/5A

Nominal Power
  • Up to 30VA

Accuracy Class
  • Classes 0.3, Class 1.0 or Class 0.5 depending on the size

Terminal
  • Screw-covered terminals

Box
  • Polycarbonate. Self-extinguishing

Mounting
  • On cable or bar

Operating ambient temperature
  • -25 C ~ +85 C

Primary conductor
  • 80 x 120 mm

Round conductor
  • Diameter 80 mm

Number of inputs
  • 1 input

Short-time thermal current
  • Ith = 60 kA

Continuous thermal current
  • Id=1 * In

Nominal frequency
  • 50Hz … 60Hz

Overvoltage current limiting factor
  • FS 5

Test voltage
  • 3kV for 1min

System Max Voltage
  • 0.72kV

Applicable Standards
  • IEC 60044-1

  • IEC 61869-2

  • VDE 0414-1

  • DIN57414

  • BS3938

  • BS7626

  • EN 61869-2

Diagrams and Dimensions

Reference Tables

Opening
(mm)
Series Ratio (A) Accuracy Class Power (VA)
80 x 120 CTK812-400/5 400/5A 3 2.5
CTK812-500/5 500/5A 1 2.5
CTK812-600/5 600/5A 1 5
CTK812-800/5 800/5A 1 10
CTK812-1000/5 1000/5A 1 10
CTK812-1250/5 1250/5A 0.5 10
CTK812-1600/5 1600/5A 0.5 10
CTK812-2000/5 2000/5A 0.5 15
CTK812-2500/5 2500/5A 0.5 15
CTK812-3000/5 3000/5A 0.5 30