Technical sheet
Designation | Type | KMC12 | KMC25 | KMC50 | KMC75 | |
---|---|---|---|---|---|---|
Capacitor power at rated voltage 50/60Hz | 230V 400-440V 500-550V 660-690V |
/kvar /kvar /kvar /kvar |
6.7 12.5 15 18 |
14 25 30 35 |
29 50 60 70 |
38 75 80 105 |
Rated operational current Ie/AC-6b at 400V | A | 18 | 36 | 72 | 108 | |
Rated operational current Ith at 400V | A | 25 | 50 | 100 | 150 | |
Isolation voltage Ui | V | 690 | 1000 | |||
Operating ambient temperature | °C | de -25 à +55 | ||||
Impulse withstand voltage Uimp | kV | 8 | ||||
Coil power consumption at cold state | When switching on f.p. Triggered f.p. |
VA VA VA VA |
62 0,75 7 0,3 |
65 0,75 8 0,3 |
155 0,6 12 0,29 |
204 0,54 16 0,26 |
Coil | Voltage tolerances Tightening torque Clamping screw type |
Nm | 0,85 – 1,1 UN 0,8 M3,5/PZ2 |
|||
Degree of protection | IP 20 | |||||
Maximum fuse rating | Main circuit gL/gG Auxiliary circuit |
A A |
35 16 |
63 16 |
125 16 |
160 16 |
Frequency of switching operations | c/h | 240 | 120 | 100 | 100 | |
Electrical endurance | min | 250.000 | 125.000 | 100.000 | ||
Conductor dimensions (Power circuit) |
Multi-wire cable
Clamping screw |
mm2 | 1.5-6
M4 |
2.5-10
M4 |
16-35
M6 |
25-50
M8 4 – 4.5 Nm |
Conductor dimensions (Control circuit) |
Multi-wire cable Clamping screw Screw head type Tightening torque |
mm2 mm2 |
1-2,5 0,75-1,5 M3,5 |
|||
Maximum load of auxiliary contacts – Current at 35°C | A | 10 | 16 | |||
Rated AC operational current Ie/AC15 under: | 230V 400V 500V 690V |
A A A A |
6 4 2 1 |
10 6 4 2 |