How does the RCMI converter work?
The integration function of the RCMI converter is essential to balance the output signal of the Rogowski coils and shift it by 90°. The integrator consists of an active electronic circuit with negligible offset and good linearity. The output voltage signal from the Rogowski coil is converted into a standard 1 A signal.
The output voltage signal from the passive Rogowski coil is proportional to the frequency of the measured current. The equalizer installed ensures a linear signal to the primary current over a wide frequency range.
When ordering in conjunction with the RCM Rogowski coil, the primary nominal current must be specified. This results in a fixed transformation ratio, similar to a standard transformer. For example, 1000/1 A: The main measurement range of 0 to 1000 A is mapped to the secondary measurement range of 0 to 1 A.
Typical applications
Advantages of the RCMI converter:
Dimensions
Technical characteristics
RCMI-01 | RCMI-03 | |
---|---|---|
Number of phases | 1 | 3 |
Nominal output current | 1A AC rms | |
Max output current (overload) | 1,5A AC rms | |
Nominal primary currents (A) | 100, 250, 400, 600, 1000, 1500, 3000, 6000 | |
Transmission accuracy | 0.5% (at 1% of the nominal primary current @25°C) | |
Phase Error | <= 0.5° | |
Linearity | +/- 0.2% of measured value (at 10 to 120% of nominal current) | |
Bandwidth | 30 Hz to 5 kHz | |
Max load per phase | 0.5 Ohm | |
Power consumption | 10 W | |
Output at 0 A (no drift) | <= 0.01 A | |
Temperature drift | 200 ppm/K | |
Weight | 185 g | |
Dimensions | 114 x 100 x 22.5 mm | |
Supply voltage | 12V DC | |
Operating temperature range | -30°C to +70°C | |
Storage temperature range | -30°C to +70°C | |
Relative humidity | Maximum 80% non-condensing | |
Protection | IP 20 | |
Certification | CE – Cmim |
Technical characteristics
Installation and Connection
Code | Designation | Nominal current | Rogowski coil compatible |
---|---|---|---|
RCMI-03-0600M | 1A measurement converter for 3 Rogowski Coils R-36 |
600A | RCM-36 |
RCMI-03-1000M | 1A measurement converter for 3 Rogowski Coils R-100 |
1000A | RCM-100 |
RCMI-03-3000M | 1A measurement converter for 3 Rogowski Coils R-150 |
3000A | RCM-150 |
RCMI-03-6000M | 1A measurement converter for 3 Rogowski Coils R-200 |
6000A | RCM-200 |
RCMI-03-1000S | 1A measurement converter for 3 Rogowski Coils with 100mV/kA output |
1000A | 3ème partie -100mV / 1kA |
RCMI-01-0600M | 1A measurement converter for 1 Rogowski Coil RCM-36 |
600A | RCM-36 |
RCMI-01-1000M | 1A measurement converter for 1 Rogowski Coil RCM-100 |
1000A | RCM-100 |
RCMI-01-3000M | 1A measurement converter for 1 Rogowski Coil RCM-150 |
3000A | RCM-150 |
RCMI-01-6000M | 1A measurement converter for 1 Rogowski Coil RCM-200 |
6000A | RCM-200 |
RCMI-01-1000S | 1A measurement converter for 1 Rogowski Coil with 100mV/kA output |
1000A | 3ème partie -100mV / 1kA |