Technical characteristics
General features | |
---|---|
Power (kVA) | Power range from 1 kVA to 3,200 kVA |
Technology | Thyristor Technology, fast voltage regulation, maintenance-free design |
Thyristor Configuration |
|
Inputs | |
---|---|
Nominal input voltage | Three-phase model: 400V AC three-phase + Neutral + Ground Model single-phase: 230V AC single-phase + Neutral + Ground (Different voltages are available as an option) |
Voltage tolerance | Model XS : -15%, +15% Model S : -25%,+15% Model M : -35%,+15% Model L : -50%, +15% |
Frequency | 50Hz. +/-5% (60Hz. in option) |
Outputs | |
---|---|
Nominal input voltage | Three-phase model: 400V AC three-phase + Neutral + Ground Model single-phase: 230V AC single-phase + Neutral + Ground (Different voltages are available as an option) |
Voltage tolerance | Between +/-1% and +/-5% (in option) |
Frequency | 50Hz. +/-5% |
Overload capacity | 125% 1min. 150% 10sec. 151% and above for 0.2sec |
Response time | 20msec |
Correction time | 100msec. – 200msec |
Efficiency | >97% typical |
Management, control, and communication interfaces | |
---|---|
Control panel with LCD display | LCD display 4×20 and schematic diagram Input voltage, output voltage, load percentage, frequency, information and error status, installation parameters |
Control panel screen | 7″ touchscreen Input voltage, output voltage, load percentage, frequency, information and error status, installation parameters |
Remote management interface (optional) | Remote management via web browser with Ethernet connection (optional) Modbus RTU with RS485 connection (optional) |
Management, control, and communication interfaces | |
---|---|
Voltage protection | Electronic protection for low voltage and high voltage |
Current protection | Input circuit breaker (output circuit breaker on request) |
Overload protection | Electronic overload protection (1min. at 125% overload, 10sec. at 150% overload, 0.2sec. at >151% overload >151%) |
Overheating protection | Electronic protection against overheating (the fan starts at 50°C. The load power is cut off at 80°C). |
Surge arrester | Surge protector Class-I or Class-II (optional) |
Environmental conditions | |
---|---|
Operating temperature | -10°C ~+50°C |
Operating altitude | 1.500m |
Humidity | 90% non-condensing |
Acoustic noise | <55dB (at a distance of one meter with closed door) |
Cabinet features | |
---|---|
Type – Protection class | Free-standing modular cabinet, interior IP21 type (Protection class: IP54 and above. Types of outdoor cabinets are optional) |
Paint – Color | Epoxy-Polyester powder coating – RAL 7035 |
Cooling | Forced air cooling with fan controlled by thermostat |