Environment

  • Installation: Indoor

  • Ambient Temperature: -5°C to 45°C

  • Average Daily Temperature: Maximum +35°C

  • Humidity: Up to 95%
  • Maximum Altitude: 2000m

GENERAL CHARACTERISTICS

Electrical Specifications
Nominal Voltage: 415 V – 50 Hz
Capacity Tolerance: -5%, +5%
Connection Type: Three-phase
Power Loss < 6 W/kVAr
Maximum Allowable Current
(with thermal protection included)
1.12 In with a tuning rank of 2.7
Maximum Allowable Voltage 1.1 x Un, 8h every 24h
Overload Protection CHL Protection Alarm (Capacitor Harmonic Load)
Isolation Voltage 690 V
Shock Withstand Voltage 8 kV
Box
Degree of protection IP42
Color RAL 7035
Degree of Mechanical Resistance IK10
Varmetric Relay
Genius® Genius® A316
Head Protection
Without circuit breaker Direct connection to busbar
The compensation bank must be protected upstream by a circuit breaker
With Main Switch Rotary Handle Switch-Disconnector
The compensation bank must be protected upstream by a circuit breaker
With Circuit Breaker Molded Case Circuit Breaker with Rotary Handle
Steps
Type of Capacitors VARCap® 525 V – 50 Hz
Maximum Overload: Up to 2.0 In
Maximum Inrush Current: ≤500 In
Operational Ambient Temperature: -40°C – +60°C
Overvoltage Protection for all 3 Phases
Discharge Resistance 50 V – 1 min
Self Anti-harmonics VARSelf® 14%
Protection against overheating by integrated thermostat
Contactors KMC Range, dedicated to capacitor switching
Step Protection By gG-type fuse or by choice of Molded Case Circuit Breaker
Temperature Control
Double Control By Thermostat and by Genius® controller
Communication
ModBus RS485
Installation
Auxiliary Power Supply Transformer 400/230 V included
CT (Not included) >5 VA – secondary1 A or 5 A
To be installed upstream of the load and the compensation bank
Emergency Group Contact Input provided for the source changeover contact
Alarm Contact Available for remote alarm reporting
Dimensions
See the reference table